Fire Alarm Battery Sizer

Standby plus alarm energy split per NFPA 72. 4 inputs, 4 outputs.

Inputs

Load

Quiescent panel current.

NFPA 72 default is 24 h.

Full alarm load.

NFPA 72 default is 5 min.

Result

Alarm energy
0.17 Ah
Required capacity
14.6 Ah
Standby energy
12.00 Ah
Standard battery
18 Ah
Screening calculation only. Verify against NEC articles cited on the page and the equipment nameplate; the authority having jurisdiction governs.