Load, wire, protection, then heat.

Methodology

Total the load with demand

List every load in kW or FLA, group motors, heaters, and controls, then apply a demand factor. Size feeders at 125 percent of the continuous portion.

Choose wire for ampacity and drop

Ampacity follows NEC 310 for the temperature rating; voltage drop follows 2 x K x I x L / cmil (single-phase and DC) or sqrt(3) x K x I x L / cmil (three-phase). The larger of the two rules wins.

Select protection per NEC 240 and 430

Branch protection uses standard sizes up to the next rating; motor branches reference the 175 percent inverse-time rule; overloads follow 115/125 percent of FLA.

Verify against the spreadsheet

Recompute one feeder by hand: demand kW, feeder amps, drop percent, breaker size. If your numbers match the calculator, the inputs are ready for every tool on this site.